annunciator
Tel: (516) 599-4875
 
annunciator home page annunciators site map View Your Cart Checkout
sbg_g1.gif
sbg1.gif
 
You are here : Home > Remote Terminal Unit For Substation Applicaitons
subangle_blu.gif
Remote Terminal Unit for Substation Applications
annunciator_t3.gif

Substation Remote Terminal Unit – PE 1800

PE 1800
zooms_off.gif

Overview

The PE 1800 RTU is an advanced Substation Remote Terminal Unit that operates as a Stand Alone RTU using its Built-in Display Status LED’s or in conjunction with any Puleo Annunciator. Multiple Serial ports allow the RTU to simultaneous act as Master and Slave devices. As a Master it acts as a Data Concentrator collecting and processing data from Intelligent Electronic
Devices (IED’s) such as Protection Relays and Meters. As a slave it reports the status of the Alarm Inputs / collected IED’s, to your system and responds to your systems Control commands. The RTU supports most Protocols and can be used as a Protocol Converter.

Downloadable Tech Manual
PE 1800 Tech Manual

Protocols
Supports Multiple Protocols in Real Time;

  • Master & Slave: DNP3, Modbus, IEC870-5-101, CDC II
  • Master: IEC870-5-103, Cooper 2179
  • Slave: L&G8979

Alarm Inputs

  • 48 Optical-Isolated Alarm Inputs with Status LED’s
  • 125 VDC External Wetting or 12Vdc internal Wetting Voltage
  • Sequence of Events Recorder with 1 ms resolution accuracy
  • Configurable debounce time (2 - 255 ms) with Chatter Filter
  • Can be configured as Accumulators

Control Outputs

  • 8 Control Outputs with Status LED’s
  • Output Relays rated .3A @ 125V DC/AC or 1A @ 30 VDC

Communications

  • 4 RS232/RS422 Device Ports configurable as Master or Slave devices
  • Front Panel Maintenance Port (configurable as another Device Port)
  • Supports Baud Rates from 300 to 38.4K

Other Features

  • IRIG-B Time Synchronization
  • Real Time Clock/Calendar with battery backup
  • Watchdog Timer
  • Built-in Diagnostics

Power / Physical Dimension / Operating Environment

  • 125 VDC or 110 VAC @ 25 Watts
  • I/O Surge Protection meets ANSI/IEEE C37.90.1
  • 19”/23” Rack or Panel Mounting
  • Temperature Range: -40°C to +85°C
  • Humidity: < 95%, non-condensing

PE 1800 - Rear Panel Layout

PE 1800
zooms_off.gif

Front Panel Maintenance Port
maintenance port

Compact 1 RU Chassis has all permanent I/O connections located on rear panel.

Convenient Front Panel Access for RTU configuration and maintenance using Puleo PE View and PE Config software. RTU configuration is stored in both SRAM and Flash memory for security.

This port can also be used as a 5th Device Port.


Downloadable Tech Manual
PE 1800 Tech Manual

backtotop.gif
Home | Company History | Contact us |
Copyright © 2008 Puleo Electronics Inc. All rights reserved.

- Partner Sites -
alarms and controls
25 pair cable
fuse panels